10
Program feature or option
Permitted in
UL864? Y/N
Possible settings
Settings permitted in UL 864
3
01 EVENT DISPLAY LOCK
N
0 = disable
1 = enable
Must be set to “1” (enable).
3
12 ZN TYPE 18 DELAY
USE
N
0 = disable
1 = enable
Must be set to “0” (disable).
3
13 “SUPV” ON OPEN AND
SHORT (APPLIES TO ZONE
TYPE 18
N 0 = Trouble on open/Supv on
short
1 = Supv on open/Supv on short
Must be set to “0”.
3
14 W.F. ALARM SILENCE
OPT.
N
0 = Silenced by User Code +
OFF
1 = Silenced when zone restores
Must be set to “0” (Silenced by
User Code + OFF).
3
16 ZONE TYP 17/18 DLY
N
Enter 01-15 times 2 seconds
Enter 00 for no delay
Must be set to 00 (no delay).
3
18 EXTENDED DLY FOR
TYP 17/18
N
0 = no extended delay
1 = multiply delay by 4
Must be set to 0 (no extended
delay).
3
20 TRIG OUTS FUNC SEL
N
0 = remote keypad sounder
1 = keyswitch LEDs
Must be set to 0 (remote keypad
sounder).
3
21 MAX ATEMPTS
Y
1-8
Must be set at 3, 4 or 5.
3
50 ZONE TYPES 16-18
REST.
N
0 = disable
1 = enable
Must be set to “1” (enable).
3
60 BELL 2, AUX RLY
TIMEOUT
Y
Enter 01-15 multiplied by 2
minutes.
00 = no timeout.
Must be set to “3” (Minimum of 6
minutes).
3
82 BURG FEATURES
ENABLED
N
0 = disable
1 = enable
Must be set to “0” (disable).
RESTRICTION FOR FIRE
RELAYS
Y
Yes
No
Restriction for # 70 must be set
to Yes when programming fire
relays.
Programming Field Settings for ULC304 Compliance
NOTICE TO USERS, INSTALLERS, AUTHORITIES HAVING JURISDICTION,
AND OTHER INVOLVED PARTIES
This product incorporates field-programmable software. In order for the product to comply with the
requirements in the Standard for Signal Receiving Centre and Premise Burglar Alarm Control Units ULC
S304, certain programming features or options must be limited to specific values or not used at all as
indicated below.
Program feature or
option
Possible settings
Settings permitted in ULC S304
38 PREVENT ZONE XXX
BYPASS (PARTITION
SPECIFIC)
Enter a zone number (001-032).
Enter 000 if all zones can be
bypassed.
Must be set to “000” (all zones can be bypassed).
1
58 ENABLE 5800 RF FORCE
ARM
0 = disable
1 = enable
Must be set to “0” (disable).
2
03 ULC S304 ENABLE
0 = disable
1 = enable
Must be set to “1” (enabled).
2
08 FORCE-ARM ENABLE
(PARTITION SPECIFIC)
0 = disable
1 = enable
Must be set to “0” (disable).