9
Program feature or option
Permitted in
UL864? Y/N
Settings permitted in UL 864
1∗
45 EXIT DELAY
SOUNDING (PARTITION
SPECIFIC)
N
0 = disable
1 = enable
Must be set to “0” (disable) for
partition 1.
1∗
48 RF KEYPAD ASSIGN 1-
8=PART. 0=NO
N 0 = none
1-8 = partition number
Not used. Must be set to “0”.
1∗
49 SUPPRESS TX
SUPERV. SOUND
N
0 = disable
1 = enable
Must be set to “0” (disable).
1∗
53 DOWNLOAD
CALLBACK
N
0 = callback required
1 = no callback required
Must be set to “0” (callback
required).
1∗
57 ENABLE 5800 RF
BUTTON GLOBAL ARM
N
0 = disable
1 = enable
Must be set to “0” (disable).
1∗
58 ENABLE 5800 RF
FORCE ARM
N
0 = disable
1 = enable
Must be set to “0” (disable).
1∗
60 ZONE 5/AUDIO ALARM
VER.
N
0 = disable
1 = enable
Must be set to “0” (disable).
1∗
72 PRINTER ON-LINE
MODE
N 0 = disable
1 = enable
Not used. Must be set to “0”.
1∗
76 ACCESS RELAY #
(PARTITION SPECIFIC)
N
01-96 = relay number
00 = relay not used.
Must be set to “00” (relay not
used) for partition 1.
1∗
78 EXT. HOME CONTROL
EVT
N 1 = extended
0 = limited
Not used. Must be set to “0”.
1∗
79 HOME CONTROL
EVENTS
N 0 = disable
1 = enable
Not used. Must be set to “0” in
each entry.
1∗
80 LOG-FAULTS &
RESTORES
N 0 = disable
1 = enable
Not used. Must be set to “0”.
2∗
07 AUTO-DISARM DELAY
(PARTITION SPECIFIC)
N
00 = no delay.
01-14 times 4 minutes (04-56)
delay.
15 = no auto disarming.
Must be set to “15” (no auto
disarming) for partition 1.
2∗
18 ENABLE GOTO FOR
PARTITION (PARTITION
SPECIFIC)
N
0 = disable
1 = enable
Must be set to “0” (disable) for
partition 1.
2∗
22 DISPLAY OTHER FIRE
ALARMS (PARTITION
SPECIFIC)
N
0 = disable
1 = enable
Must be set to “0” (disable) for
partition 1.
2∗
23 DISPLAY OTHER
BURG & PANIC
(INCLUDING CO ALARMS)
(PARTITION SPECIFIC)
N
0 = disable
1 = enable
Must be set to “0” (disable) for
partition 1.
2∗
24 DISPLAY TROUBLES
OF OTHER PARTITIONS
(PARTITION SPECIFIC)
N
0 = disable
1 = enable
Must be set to “0” (disable) for
partition 1.