8
Program feature or option
Permitted in
UL864? Y/N
Settings permitted in
UL 864
∗
28 POWER-UP IN PREV.
STATE
Y
0 = disable
1 = enable
Must be set to “1” (enable).
∗
37 DOWNLOAD COMMAND
ENABLES
N
0 = disable
1 = enable
Must be set to “0” for all
entries (disable).
∗
41 NORMALLY CLOSED OR
EOLR (ZONES 3-8)
N
0 = EOLR supervision
1 = N.C. loops
Must be set to “0” (EOLR
Supervision).
∗
42 DIAL TONE PAUSE
Y
Enter the wait time for dial tone
detection:
0 = 5 seconds; 1 = 11 seconds; 2 = 30
seconds.
Must be set to “0” (5 seconds).
∗
44 RING DETECTION
COUNT
N
Enter 00 to disable ring detection.
Enter 01-14 for ring counts of 1-14.
Enter 15 to select Answering
Machine Defeat Mode
Must be set to “00” (disable).
∗
56 DYNAMIC SIGNAL
DELAY
Y
Enter 00-15 times 15 seconds.
Must be set to “6” (90
seconds).
∗
77 AUTO TRBL RSTR
Y
0 = disable
1 = restore troubles only
2 = restore troubles and fire alarms
Must be set to “1” (restore
troubles only).
∗
80 ZONE TYPE 9 -10, 14
RESTORE
N
0 = disable
1 = enable
Must be set to “1” (enable) for
zone type 9.
1∗
12 PROGRAM
NOTIFICATION
Y
0 = no
1 = yes
Must be set to “1” (yes).
1∗
13 SYS. SENSOR REV.
RELAY
N 0=use neither Zone 1 or Zone 2
inputs
1=use Zone 1 input;
2=use Zone 2 input;
3=use Zone 1 and Zone 2 inputs.
Not Used. Must be set to “0”.
1∗
18 AFFECTS LOBBY
(PARTITION – SPECIFIC)
N
0 = disable
1 = enable
Must be set to “0” (disabled)
for partition 1.
1∗
19 ARMS LOBBY
(PARTITION – SPECIFIC)
N
0 = disable
1 = enable
Must be set to “0” (disabled)
for partition 1.
1∗
22 thru
1∗
25 CROSS-
ZONING PAIRS (1 – 4)
N
Enter 001-032
Enter 000,000 to disable
Must be set to “000,000”
(disabled) for fire zones.
1∗
28 RF TX LOW BATTERY
SOUND
N
0 = disarmed state only
1 = both armed and disarmed states
Must be set to “1” (both
armed and disarmed states).
1∗
29 RF TX LOW BATTERY
REPORTING
N
0 = disable
1 = enable
Must be set to “1” (enable).
1∗
30 RF RCVR CHECK-IN
INTERVAL
N
Enter 02–15 times 2 hours (4–30
hours)
Enter 00 to disable receiver
supervision
Maximum is 02 (4 hours) for
fire installations.
1∗
31 RF TX CHECK-IN
INTERVAL
N
Enter 02–15 times 2 hours (4–30
hours)
Enter 00 to disable transmitter
supervision
Maximum is 02 (4 hours) for
fire installations.
1∗
35 ACS DLR ENABLES
N 0 = disable
1 = enable
Not used. Must be set to “0”.
1∗
44 RF KEYPAD TAMPER
DETECTION
N 0 = disable
1 = enable
Not used. Must be set to “0”.