V8200A,C,H,M AND VR8200A,C,H,M CONTINUOUS PILOT COMBINATION GAS CONTROLS
69-0422—03 6
Turn On Main Burner
Follow instructions provided by appliance manufacturer or 
turn thermostat up to call for heat.
Adjust Pilot Flame
The pilot flame should envelop 3/8 to 1/2 in. 
(10 to 13 mm) of the tip of the thermocouple. Refer to 
Fig. 9.
1. Remove pilot adjustment cover screw. 
Refer to Fig. 4.
2. Turn inner adjustment screw clockwise   to 
decrease or counterclockwise   to increase 
pilot flame.
3. Always replace cover screw after adjustment. 
Tighten firmly to prevent gas leakage.
Fig. 9. Proper Flame Adjustment.
Check and Adjust Gas Input to Main Burner 
1. Do not exceed input rating stamped on 
appliance nameplate, or manufacturer's 
recommended burner orifice pressure for size 
orifice(s) used. Make certain primary air supply 
to main burner is properly adjusted for complete 
combustion. Follow appliance manufacturer's 
instructions.
2. IF CHECKING GAS INPUT BY CLOCKING 
GAS METER: Make certain there is no gas flow 
through the meter other than to the appliance 
being checked. Other appliances must remain 
off with their pilots extinguished (or their 
consumption must be deducted from the meter 
reading). Convert flow rate to Btuh as described 
in form 70-2602, Gas Controls Handbook, and 
compare to the Btuh input rating on appliance 
nameplate.
3. IF CHECKING GAS INPUT WITH 
MANOMETER: Make certain gas control is in 
PILOT position before removing outlet pressure 
tap plug to connect manometer (pressure 
gauge). Also turn gas control knob back to 
PILOT when removing gauge and replacing 
plug. Before removing inlet pressure tap plug, 
shut off gas supply at the manual valve in the 
gas piping to the appliance or, for LP, at the 
tank. Also shut off gas supply before 
disconnecting manometer and replacing plug. 
Repeat Gas Leak Test at plug with main burner 
operating.
Standard Pressure Regulator
1. Check the manifold pressure listed on the appliance 
nameplate. Gas control outlet pressure should 
match the nameplate.
2. With main burner operating, check gas control flow 
rate using the meter clocking method or pressure 
using a manometer connected to the outlet 
pressure tap on the gas control. Refer to Fig. 4.
3. If necessary, adjust pressure regulator to match 
appliance rating. Refer to Table 7 for factory set 
nominal outlet pressure and adjustment range.
a. Remove pressure regulator adjustment cap and 
screw.
b. Using screwdriver, turn inner adjustment screw 
clockwise   to increase or counterclockwise 
 to decrease gas pressure to burner.
c. Always replace cap screw and tighten firmly to 
ensure proper operation.
4. If desired outlet pressure or flow rate cannot be 
achieved by adjusting the control, check the control 
inlet pressure using a manometer at the inlet 
pressure tap. If inlet pressure is in normal range 
(refer to Table 7), replace the control. Otherwise, 
take the necessary steps to provide proper gas 
pressure on the control.
Step-Opening and Slow Opening 
Pressure Regulator
1. Check the full rate manifold pressure listed on the 
appliance nameplate. Gas control full rate outlet 
pressure should match this rating.
2. With main burner operating, check the control flow 
rate using the meter clocking method or pressure 
using a manometer connected to outlet pressure 
tap on the control. Refer to Fig. 4.
3. If necessary, adjust pressure regulator to match 
appliance rating. Refer to Table 7 for factory set 
nominal outlet pressure and adjustment range.
a. Remove pressure regulator adjustment cap 
screw.
b. Using screwdriver, turn inner adjustment screw 
clockwise   to increase or counterclockwise 
   to decrease gas pressure to burner
c. Always replace cap screw and tighten firmly to 
ensure proper operation.
4. If desired outlet pressure or flow rate cannot be 
achieved by adjusting the control, check the inlet 
pressure using a manometer at inlet pressure tap or 
upstream of the gas control. If inlet pressure is in 
the normal range (refer to Table 7), replace the 
existing control. Otherwise, take the necessary 
steps to provide proper gas pressure to the control.
5. STEP-OPENING PRESSURE REGULATORS 
ONLY. Carefully check burner lightoff at step 
pressure. Make sure burner lights smoothly and 
without flashback to orifice. Make sure all ports 
remain lit. Cycle burner several times, allowing at 
least 30 seconds between cycles for regulator to 
resume step function. Repeat after allowing burner 
to cool. Readjust full rate outlet pressure if 
necessary to improve lightoff characteristics.
M3086B
PROPER FLAME
ADJUSTMENT
3/8 TO 1/2 IN.
(10 TO 13 MM)
THERMOCOUPLE