Fig. 66. Connecting to a screw terminal 
 
IMPORTANT 
If there already are additional transformers, for 
example supplying actuators or active sensors, 
connect the 24 Vac (-) (secondary side) of the 
transformers together. 
 
  8.  Attach the terminal blocks to the housing as shown in 
Fig. 67. 
 
 
Fig. 67. Attaching screw terminal block 
 
Table 14. Accuracy of analog input sensors 
range 
measurement error 
(without sensor tolerance) 
Pt1000  NTC (20k ohms) 
-58 to –4 °F (-50 to –20 °C)   1.2 K   5.0 K 
-4 to 32 °F (-20 to 0 °C)   0.7 K   1.0 K 
32 to 86 °F (0 to 30 °C)   0.5 K   0.3 K 
86 to 158 °F (30 to 70 °C)   0.7 K   0.5 K 
158 to 212 °F (70 to 100 °C)   1.2 K   1.0 K 
212 to 266 °F (100 to 130 °C)   1.2 K   3.0 K 
266 to 302 °F (130 to 150 °C)   1.2 K   5.5 K