Honeywell Process Solutions Wireless Dual Analog Input Interface Transmitter
28 User Manual Rev. 8
July 2012
6.4.2: Configure the Abnormal
Sampling Rate Using WMT*
1. Open the configuration dialog box (See Appendix A).
2. In the configuration dialog box click the Sampling Rates tab to dis-
play the sampling rate information as shown below.
3. Select one of the time periods from the Abnormal Sampling drop-
down list box.
4. Click OK to save and download the configuration changes to the
Transmitter.
Figure 6.12: Sampling Rates Tab
* Indicates that Menu is Disabled if Wireless Management Toolkit is detected. (See Appendix A)