Honeywell Process Solutions Wireless Dual Analog Input Interface Transmitter
Rev. 8 User Manual 31
July 2012
6.6.2: Configure the Upper and
Lower Limits Using WMT*
1. Open the configuration dialog box (See Appendix A).
2. Click the Sampling Bands tab to display the sampling bands infor-
mation as shown below.
3. Enable the Upper Limit by selecting the Use Input 1 Limit check
box.
4. Enter the Value and Time Deadband for the limit.
5. Type a message to be displayed on the Transmitter when the value is
beyond your set limit in the LCD Message box.
6. Repeat steps 3-5 for the Lower Limit.
7. Click OK to save and download the configuration changes to the
Transmitter.
Figure 6.17: Normal Upper and Lower Value
* Indicates that Menu is Disabled if Wireless Management Toolkit is detected. (See Appendix A)