EasyManuals Logo

Hoval Max-3 plus Series User Manual

Hoval Max-3 plus Series
60 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #31 background imageLoading...
Page #31 background image
314 214 283 / 00
COMMISSIONING
Heating Water
The European Standard EN 14868 and the
directive VDI 2035 must be observed.
In particular, attention must be paid to the following stipu-
lations:
cording to EN 14868).
• Plants with
- continuous oxygen intake (e.g. underfloor heating
systems without diffusion proof plastic piping) or
- intermittent oxygen intake (e.g. where frequent refill-
ing is necessary)
must be equipped with separate circuits.
least 1x yearly. According to the inhibitor manufacturer‘s
instructions, more frequent testing may be necessary.
water in existing installations (e.g. exchange of boiler)
conforms to VDI 2035.
The Directive VDI 2035 applies equally to the replace-
ment water.
New and if applicable existing installations need to be
water are made of ferrous materials and stainless steel.
On account of the danger of stress cracking corrosion
in the stainless steel section of the boiler the chloride,
nitrate and sulphate content of the heating water must
not exceed 50 mg/l.
The pH value of the heating water should lie between
8.3 and 9.5 after 6-12 weeks of heating operation.
Filling and replacement water
For a plant using Hoval boilers untreated drinking water
ing and replacement water. However, as not all drinking
VDI 2035. Should the mains water available not be
suited for use then it must be desalinated and/ or be
treated with inhibitors. The stipulations of EN 14868
must be observed.
to avoid overheating of the heating surfaces the values
given in the table should not be exceeded (dependent
on boiler performance ratings - for multi-boiler plants
rating of smallest boiler applies - and on the water con-
tent of the plant).
is used throughout the total service life of the boiler
must not exceed three times the water capacity of the
plant.
Maximum filling capacity based on VDI 2035
[mol/m
3
]
1
<0,1 0,5 1 1,5 2 2,5 3 >3,0
f°H <1 5 10 15 20 25 30 >30
d°H <0,56 2,8 5,6 8,4 11,2 14,0 16,8 >16,8
e°H <0,71 3,6 7,1 10,7 14,2 17,8 21,3 >21,3
~mg/l <10 50,0 100,0 150,0 200,0 250,0 300,0 >300
Conductance
2
<20 100,0 200,0 300,0 400,0 500,0 600,0 >600
Boiler size of the
individual boiler
50 to 200 kW NO REQUI- 50 l/kW 20 l/kW 20 l/kW
always desalinate200 to 600 kW RE- 50 l/kW 50 l/kW 20 l/kW
over 600 kW MENT
1
Sum of alkaline earths
2
If the conductance in μS/cm exceeds the tabular value an analysis of the water is necessary.
5. Commissioning
5.1 Water quality
NOTE:
No continous make-up of water should be
taking place during boiler operation. In
this event check where a leak may be oc-
curing or if pumping over is taking place.

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Hoval Max-3 plus Series and is the answer not in the manual?

Hoval Max-3 plus Series Specifications

General IconGeneral
BrandHoval
ModelMax-3 plus Series
CategoryBoiler
LanguageEnglish

Related product manuals