4 214 174 V00 KDT GLT-Modul TTE_EN.docx 20 / 26
20-071
Vol. flow pulse gen
pulse rate info 2 IMP
20
,1
5000.0
Volume flow rate sensor (pulses per litre)
4
4
20-081
Volume flow pulse
gen. offset info 2
IMP
0
-10.00
10.00
Offset (for flow rate sensor)
4
4
30-081
Alloc.inp.info 3 IMP
0=OFF
Alloc. inp. information 3 pulse:
0=OFF, 3=VE3, 6=FVT-F, 9=VE3-FE1,
12=FVT-F FE1, 15=VE3-FE2, 18=FVT-
F FE2
4
4
20-107
Name info 3 IMP
Info 3 IMP
0
13
Name info 3 IMP
4
4
20-072
Vol. flow pulse gen
pulse rate info 3 IMP
20
,1
5000.0
Volume flow rate sensor (pulses per litre)
4
4
20-082
Offset VIG Info3 IMP
0
-10.00
10.00
Offset (for flow rate sensor)
4
4
30-076
Alloc.inp.info 1
0-10V
0=OFF
Alloc. inp. information 1 0-10V:
0=OFF, 4=VE10V, 10=VE10V-FE1,
16=VE10VFE2
4
4
20-100
Conversion for 10V
info 1
10
10
10000
Conversion for 10V
Info 1
4
4
20-095
Name info 1
0-10V
Info 1 VE
0-10V
0
13
Name information 1
0-10V
0
4
30-077
Alloc.inp.info 2
0-10V
0=OFF
Alloc. inp. information 2 0-10V:
0=OFF, 4=VE10V, 10=VE10V-FE1,
16=VE10VFE2
4
4
20-101
Conversion for 10V
info 2
10
10
10000
Conversion for 10V
Info 2
4
4
20-096
Name info 2
0-10V
Info 2 VE
0-10V
0
13
Name information 2
0-10V
0
4
30-078
Alloc.inp.info 3
0-10V
0=OFF
Alloc. inp. information 3 0-10V:
0=OFF, 4=VE10V, 10=VE10V-FE1,
16=VE10VFE2
4
4
20-102
Conversion for 10V
info 3
10
10
10000
Conversion for 10V
Info 3
4
4
20-097
Name info 3
0-10V
Info 3 VE
0-10V
0
13
Name information 3
0-10V:
13. Date time menu
Parameter
Designation
Value
Min.
Max.
Comment
R
W
02-070
Date
2015-01-16
0
65535
Date
0
0
02-072
Time of day
14:47
0
1439
Time of day
0
0
02-073
Weekday
Friday
0
0
Weekday
0
7