Cooling
Plan the installation site for adequate ventilation:
Leave a minimum of 30 cm (11.81 in) of clearance at the front and rear of the switch. (Perforated rack
doors are acceptable within the 30cm spacing.)
NOTE: Air ow into and out of the switch is indicated by the arrows in the image below.
Ensure that the rack for the switch is well ventilated, with minimal airow obstruction at the front and
rear.
The installation site HVAC system must be capable of removing all heat generated by the switch.
Verify that the airow design of the chassis is compatible with the airow design of the installation site.
Figure 5: Aruba 6405 Switch cooling air ow
30 cm (11.01 in)
30 cm (11.01 in)
Figure 6: Aruba 6410 Switch cooling air ow
30 cm (11.01 in)
30 cm (11.01 in)
18 Aruba 6400 Switch Series Installation and Getting Started