Resolving voltage and temperature warnings 53
During a shutdown, the cooling fans do not shut off. This allows the enclosure to continue cooling.
Temperature sensors
Extreme high and low temperatures can cause significant damage if they go unnoticed. When a temperature fault is
reported, it must be remedied as quickly as possible to avoid system damage. This can be done by warming or cooling
the installation location.
When a power supply sensor goes out of range, the Fault/ID LED illuminates amber and an event is logged.
Power supply module voltage sensors
Power supply voltage sensors ensure that the enclosure power supply voltage is within normal ranges. There are three
voltage sensors per power supply.
Table 24 Controller platform temperature sensor descriptions
Description Normal operating
range
Warning operating
range
Critical operating
range
Shutdown
values
CPU temperature
(internal digital thermal sensor)
2°C–98°C 0°C–1°C,
99°C–104°C
None ≤ 0°C
≥ 104°C
SAS2008 internal digital sensor 3°C–112°C 0°C–2°C,
113°C–115°C
None ≤ 0°C
≥ 115°C
Supercapacitor pack thermistor 0°C–50°C None None None
Onboard temperature 1 0°C–70°C None None None
Onboard temperature 2 0°C–70°C None None None
Onboard temperature 3 0°C–70°C None None None
Table 25 Power supply temperature sensor descriptions
Description Normal operating range
Power Supply 1 temperature –10°C–80°C
Power Supply 2 temperature –10°C–80°C
Table 26 Voltage sensor descriptions
Sensor Event/Fault LED condition
Power supply 1 voltage, 12V < 11.00V
> 13.00V
Power supply 1 voltage, 5V < 4.00V
> 6.00V
Power supply 1 voltage, 3.3V < 3.00V
> 3.80V