Shenzhen Hpmont Technology Co., Ltd. Chapter 10 Parameter
HD09 Series User Manual V1.1 -81-
Function
Setting Range
Default
Unit
Setting
2: The fan runs continuously when
power on
F19.08
Cooling fan controls
delaying time
0.0 - 600.0s 30.0s 0.1s
×
F19.12
Instantaneous loss of
power and no stop
function selection
0: Disable instantaneous loss and no
stop
1: Enbale instantaneous loss and no
stop
0 1
×
F19.13
Instant stop function
deceleration time
0.01 - 600.00s 5.00s 0.01s
○
F19.14
Voltage rerise judgement
time for Instantaneous loss
of power and no downtime
0.00 - 10.00s 0.10s 0.01s
○
F19.15
Voltage judgement for
Instantaneous loss of
power and no downtime
0 - 999V
220V
inverter:
248V
380V
inverter:
430V
1V
×
F19.18
Protection of stall
overvoltage
0: Disabled (with braking resistance)
1: Enabled
1 1
×
F19.19 Stall overvoltage point 0 - 999V
Dependent
on HD09
1V
×
F19.20
Auto current limiting
selection
0: Disabled
1: Enabled in Acc. / Dec. running
process, but disabled in constant speed
runnng process
2: Enabled both in Acc. / Dec. and in
constant speed running proces
1 1
×
F19.21
Auto current limiting
threshold
20.0 - 200.0% 150.0% 0.1%
×
F19.22
Deceleration time at auto
current limiting
0.00 - 600.00s 0.00s 0.01s
×
F19.23
Enabled mode of terminal
run command
0: Rise edge enabled mode
1: Level enabled mode
0 1
○
F19.24
Action voltage of braking
unit
630 - 750V
Dependent
on HD09
1V
×