- JJamie ChapmanAug 20, 2025
If your HTP Boiler isn't detecting a flame, here's what you can do: First, watch the igniter through the observation window. If there's no spark, check the spark electrode for the proper ¼” gap. Remove any corrosion from the spark electrode and flame rectifier probe. If there is a spark but no flame, check the gas supply to the boiler. If there is a flame, check the flame sensor. Also, check for any flue blockage or condensate blocks.