| 71
Professional humidity switch PLS1000
NOTE: Relays T1 / T2 or F1 / F2 are switched off if the indoor sensor or
outdoor sensor is defective or not connected.
7.5 MANUAL CONTROL
In this mode, all potential-free relays T1, F1, T2 and F2 can be manually
switched on and off.
MODE: MANUAL
The following menu points are displayed and can be changed:
MODUS: MANUELL / MODE: MANUAL CONTROL
RELAIS T1 EIN/AUS / RELAY T1 ON/OFF
RELAIS F1 EIN/AUS / RELAY F1 ON/OFF
RELAIS T2 EIN/AUS / RELAY T2 ON/OFF
RELAIS F2 EIN/AUS / RELAY F2 ON/OFF
The switching state of the relays can be set using the
,
, OK buttons.
7.6 RESET
In this menu item, all settings can be reset to factory settings (delivery status).
HUMIDITY
TIME
Switch-on point
F1 on
F1 off
Switch-off point
DEHUMIDIFY
“DEHUMIDIFY” FUNCTION IN TF-SWITCHING MODE
The “dehumidify” function is set when the set on-load humidity value is greater
than the off-set humidity value. The control is carried out by the relay F1 or F2.
Behavior of relay F1 or F2
Abbreviations:
F1 measured relative humidity at the indoor sensor
F1 EIN setpoint for the switch-on humidity
F1 AUS setpoint for the switch-off humidity
Relay F1 turns on when
F1 ≥ F1 ON
Relay T1 is switched off when
F1 ≤ F1 AUS
Modes/ functions