The cable diameter must comply with local cable standards. The factors that aect cable
selection include the rated current, cable type, routing mode, ambient temperature, and
maximum expected line loss.
Table 5-2 PE cable specications
Conductor Cross-Sectional Area S of
the AC Power Cable (Unit: mm
2
)
Conductor Cross-Sectional Area S
P
of
the PE Cable (Unit: mm
2
)
S > 35 S
P
≥ S/2
The specications are valid only if the conductors of the PE cable and AC power
cable use the same material. If the materials are dierent, ensure that the
conductor cross-sectional area of the PE cable produces a conductance
equivalent to that of the cable specied in this table. The specications of the
PE cable are subject to this table or calculated according to IEC 60364-5-54.
Connecting the PE Cable
Step 1 Secure the PE cable using the ground screw.
Figure 5-8 Cable connection
Step 2 (Optional) Apply silica gel or paint on the ground terminal to protect it against
corrosion.
----End
Connecting the AC Output Power Cable (Multi-core)
Step 1 Connect the AC cable to the terminal block.