No. Parameter Description Remarks
26 Q-U characteristic
curve
The inverter adjusts Q/S (the ratio
of the output reactive power to
apparent power) in real time
based on U/Un(%) (the ratio of
the actual power grid voltage to
the rated power grid voltage).
-
27 Q-P characteristic
curve
The inverter adjusts Q/Pn (the
ratio of the output reactive power
to the rated active power) in real
time based on P/Pn(%) (the ratio
of the actual active power to the
rated active power).
-
28 Cosφ-P/Pn
characteristic curve
The inverter adjusts the output
power factor cosφ in real time
based on P/Pn(%).
-
7.2 Operations with a USB Flash Drive
USB
ash drives of SanDisk, Netac, and Kingston are recommended. Other brands
may be incompatible.
NO TE
Delete the script le immediately after use to reduce information disclosure risks.
7.2.1 Exporting
Congurations
Procedure
1. Click Local maintenance script on the app to generate a boot script
le, see
the
FusionSolar APP and SUN2000 APP User Manual
.
2. Import the boot script
le to a PC.
(Optional) The boot script
le can be opened as a .txt le.
Figure 7-14 Boot script le