7.1.4.1 Setting Grid Parameters
Procedure
Step 1 ChooseFunction Menu > Settings > Grid Parameters to access the parameters
setting screen.
Figure 7-7 Grid parameters (advanced user)
----End
Parameters
No. Parameter Description
1 Grid Code Set this parameter based on the grid code of the country or
region where the inverter is used and the inverter application
scenario.
2 Isolation settings Set the working mode of the inverter based on the grounding
status at DC side and the connection to the power grid.
7.1.4.2 Setting Protection Parameters
Procedure
Step 1 ChooseFunction Menu > Settings > Protect Parameters to go to the parameter
setting screen.
Figure 7-8 Protection parameters (advanced user)
----End
Parameter
No. Parameter Description
1 Insulation resistance
protection threshold (MΩ)
To ensure device safety, the inverter detects the insulation
resistance of the input side with respect to ground when it
starts a self-check. If the detected value is less than the
preset value, the inverter does not connect to the grid.