EasyManua.ls Logo

Huawei Iris Hellas SUN2000 Series - Page 73

Huawei Iris Hellas SUN2000 Series
123 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Figure 7-10 Power grid parameters (special user)
----End
Parameters
No. Parameter Description
1 Grid Code Set this parameter based on the grid code of the country
or region where the inverter is used and the inverter
application scenario.
2 Isolation settings Set the working mode of the inverter based on the
grounding status at DC side and the connection to the
power grid.
3 Output mode Species whether the inverter output has a neutral wire
based on the application scenario.
4 Automatically start upon
grid recovery
Species whether to allow the inverter to automatically
start after the power grid recovers.
5 Grid connected recovery
time from grid faults (s)
Species the time after which the inverter begins
restarting after the power grid recovers.
6 Startup voltage lower
threshold of grid
connection (V)
According to the standards of certain countries and
regions, after the inverter is powered on for the rst time
for grid connection, if the power grid voltage is lower
than Startup voltage lower threshold of grid
connection, the inverter is not allowed to connect to the
grid.
SUN2000-(175KTL-H0, 185KTL-INH0, 185KTL-H1
User Manual
7 Man-Machine Interactions
Issue 05 (2020-08-30) Copyright © Huawei Technologies Co., Ltd. 65

Table of Contents

Related product manuals