OptiX OSN 7500 
Technical Manual - System Description  10 Technical Specifications 
 
Huawei Technologies Proprietary 
10-12 
10.8  Environment Requirement 
The following international standards are taken as the reference for framing the 
environment requirements. 
 
GF 014-95: Environment conditions for the communication equipment room 
 
European Telecommunication Standards  ( ETS) 300 019-1-3: Class 3.2 Partly 
temperature-controlled location 
 
NEBS GR-63-CORE: Network Equipment-Building System (NEBS) 
Requirements: Physical Protection 
10.8.1  Environment for Storage 
1.  Climate 
Table 10-18 shows the climate environment required for storing the OptiX OSN 7500. 
Table 10-18 Climate environment for storage 
Item  Range 
Altitude  ≤5000 m 
Air pressure  70 kPa–106 kPa 
Temperature 
–40°C to +70°C 
Temperature change rate 
≤1°C/min 
Relative humidity  10%–100% 
Solar radiation  ≤1120 W/s² 
Heat radiation  ≤600 W/s² 
Air speed  ≤30 m/s 
 
2.  Waterproof 
(1) The equipment is required to be stored indoors. 
(2) No accumulated water is allowed on the floor, and no water drops on the packing 
box. Keep away from auto fire fighting facilities and heating pipes where water 
leakage may occur. 
(3) If it is necessary to be stored outdoors, the following four conditions should be met: 
 
The packing box is undamaged.