Huawei OptiX OSN 7500 - Table 10-28 Density for Mechanical Active Substances; Table 10-29 Density for Chemical Active Substances

Huawei OptiX OSN 7500
118 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
OptiX OSN 7500
Technical Manual - System Description 10 Technical Specifications
Huawei Technologies Proprietary
10-18
2. Biological Environment
(1) Avoid multiplication of microbe, such as eumycete and mycete.
(2) Avoid rodentia animals such as mice.
3. Air Cleanliness
(1) No explosive, electric-conductive, magnetic-conductive or corrosive dust.
(2) The density of the mechanical active substances complies with the requirements
listed in Table 10-28.
Table 10-28 Density for mechanical active substances
Mechanical active substance Content
Dust particle 3x10
5
particles/m³
Suspending dust 0.4 mg/m³
Precipitable dust 15 mg/m²·h
Gravel 100 mg/m³
(3) The density of the chemical active substances complies with the requirements
listed in Table 10-29.
Table 10-29 Density for chemical active substances
Chemical active substance Content
SO
2
0.20 mg/m³
H
2
S 0.006 mg/m³
NH
3
0.05 mg/m³
Cl
2
0.01 mg/m³
HCl 0.10 mg/m³
HF 0.01 mg/m³
O
3
0.005 mg/m³
CO 5.0 mg/m³