PowerCube 500 (CPS300-N18A1H)
User Manual
5 Alarms and Troubleshooting
Copyright © Huawei Technologies Co., Ltd.
39
Indicator
Status
Alarm Name
Possible Cause
Solution
incorrectly set.
If yes, reset the threshold.
If no, contact Huawei
technical support.
DC Overvolt.
The DC overvoltage
alarm threshold is
incorrectly set.
1. Reset the DC overvoltage
alarm threshold and check
whether the alarm persists.
If yes, contact Huawei
technical support.
If no, no further action is
required.
DC Undervolt.
The battery voltage
is below the
undervoltage alarm
threshold after a
long-time AC
power failure.
The DC
undervoltage alarm
threshold is
incorrectly set.
1. Check whether the battery
voltage is below the
undervoltage alarm threshold
after a long-time AC power
failure.
If yes, rectify the power
grid fault.
If no, go to the next step.
2. Check whether the DC
undervoltage alarm threshold
is incorrectly set.
If yes, reset the alarm
threshold.
If no, contact Huawei
technical support.
Power module
Update Failed
The module
experiences a
power failure
during an upgrade.
The module
experiences a
communication
failure during an
upgrade.
1. Check whether the function
module experiences a power
failure.
If yes, ensure that the
function module is
properly powered on.
If no, go to the next step.
2. Check whether the solar
function unit communicates
properly. Ensure that the
communication is proper,
continue the upgrade, and
check whether the alarm
persists.
If yes, replace the
function module.
If no, no further action is
required.
ESMU Missing
The lithium battery
1. Check whether the lithium

Other manuals for Huawei PowerCube 500