EasyManua.ls Logo

Huawei PowerCube 500 - Lithium Battery

Huawei PowerCube 500
67 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
PowerCube 500 (CPS300-N18A1H)
User Manual
5 Alarms and Troubleshooting
Copyright © Huawei Technologies Co., Ltd.
43
Indicator
Status
Alarm Name
Possible Cause
Solution
grounded.
The general ground
point of the site is
abnormal.
and the power distribution
box is more than 1.5 km
away from the function
module.
If yes, add a level B SPD
onsite.
If no, go to the next step.
3. Check whether the ground
point of the function module
is properly connected.
If yes, go to the next step.
If no, connect the ground
point properly.
4. Check whether the site
grounding resistance is less
than 10 ohms.
If yes, contact Huawei
technical support.
If no, repair the total
grounding resistance of
the site and decrease it to
below 10 ohms.
5.2 Lithium Battery
Table 5-2 Alarms and troubleshooting
Indicator
Status
Alarm Name
Possible Cause
Solution
Blinking
red
Low
Temperature
Protection
The battery
temperature is too
low.
The device is
faulty.
1. Check whether the
temperature control device
such as the fan or air
conditioner in the battery
compartment is abnormal.
If yes, maintain the
temperature control
device.
If no, go to the next step.
2. Reset the ESMU and check
whether the alarm is cleared.
If yes, no further action is
required.
If no, contact Huawei

Other manuals for Huawei PowerCube 500