EasyManua.ls Logo

Huawei PowerCube 500 - Page 50

Huawei PowerCube 500
67 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
PowerCube 500 (CPS300-N18A1H)
User Manual
5 Alarms and Troubleshooting
Copyright © Huawei Technologies Co., Ltd.
44
Indicator
Status
Alarm Name
Possible Cause
Solution
technical support.
Discharge
High
Temperature
Protection
The battery
temperature is too
high.
The device is
faulty.
1. Check whether the
temperature control device
such as the fan or air
conditioner in the battery
compartment is abnormal.
If yes, maintain the
temperature control
device.
If no, go to the next step.
2. Reset the ESMU and check
whether the alarm is cleared.
If yes, no further action is
required.
If no, contact Huawei
technical support.
Charge High
Temperature
Protection
The battery
temperature is too
high.
The device is
faulty.
1. Check whether the
temperature control device
such as the fan or air
conditioner in the battery
compartment is abnormal.
If yes, maintain the
temperature control
device.
If no, go to the next step.
2. Reset the ESMU and check
whether the alarm is cleared.
If yes, no further action is
required.
If no, contact Huawei
technical support.
Overcharge
Protection
The battery voltage
is too high.
The device is
faulty.
1. Handle function module
alarms and check whether the
alarm is cleared.
If yes, no further action is
required.
If no, go to the next step.
2. Charge the battery and check
whether the alarm is cleared
and battery backup time is
normal.
If yes, no further action is
required.
If no, go to the next step.
3. Replace the battery and

Other manuals for Huawei PowerCube 500