5 Alarms and Troubleshooting
Copyright © Huawei Technologies Co., Ltd.
check whether the alarm is
cleared.
If yes, no further action is
required.
If no, contact Huawei
technical support.
The battery voltage
is too low.
The device is
faulty.
1. Check whether the AC
voltage is abnormal.
If yes, rectify the power
grid fault.
If no, contact Huawei
technical support.
Discharge
Overcurrent
Protection
1. Switch off the battery circuit
breaker and check whether
the battery voltage is
abnormal.
If yes, replace the battery.
If no, go to the next step.
2. Check whether the function
module has a communication
failure alarm.
If yes, handle the alarm.
If no, contact Huawei
technical support.
Charge
Overcurrent
Protection
1. Switch off the battery circuit
breaker and check whether
the battery voltage is
abnormal.
If yes, replace the battery.
If no, go to the next step.
2. Check whether the function
module has a communication
failure alarm.
If yes, handle the alarm.
If no, contact Huawei
technical support.
Battery
Electrochemica
l Cell n Fault
An electrochemical
cell is faulty.
1. Replace the battery and
check whether the alarm is
cleared.
If yes, no further action is
required.
If no, contact Huawei
technical support.
1. Replace the device and check