ɲ /©Low Insulation Resistance alarm is still reported one minute after the
DC is supplied, check the percentage for possible short-circuit positions on the
Alarm details page and go to Step 4.
Figure E-1 Alarm details
NO TE
ɲ f¯ÝÑä²ì²üÊÊªì²üìàɲÊÃäÑ©Wväìà²ÊªàÑÊÊììÑì¯WvɆÊWvț
ìàɲÊÃäÑ©ì¯äÑÃà²Êüàìàȇf¯WvțìàɲÊÃàÝàäÊìäÝÑää²²Ã²ìăÑ©ǀɟ©Ñàì¯
ä¯Ñàìȝ²àñ²ìÝÑä²ì²ÑÊÊì¯WvɆìàɲÊÃàÝàäÊìäÝÑää²²Ã²ìăÑ©ǁǀǀɟ©Ñàì¯
short-circuit position. Other percentages indicate that the fault occurs on a PV module
or cable in the PV string.
ɲ WÑää²Ã©ñÃìÝÑä²ì²ÑÊɊfÑìÃÊñÉàÑ©WvÉÑñÃä²ÊWväìà²ÊªĂWàÊìªÑ©
possible short-circuit positions. For example, if a PV string consists of 14 PV modules
Êì¯ÝàÊìªÑ©ì¯ÝÑää²Ãä¯Ñàìȝ²àñ²ìÝÑä²ì²ÑÊ²äǃDŽɟȀì¯ÝÑää²Ã©ñÃì
ÝÑä²ì²ÑÊ²äDŽȇLJdžȖǁDŽĂǃDŽɟȗȀ²Ê²ì²Êªì¯ìì¯©ñÃì²äÃÑìÊàWvÉÑñÃDŽȀ
including the previous and the next PV modules and the cables of PV module 4. The
äÑÃà²Êüàìà¯äìì²ÑÊÝà²ä²ÑÊÑ©ɐǁWvÉÑñÃȇ
Figure E-2 Ēʲì²ÑÊ of the percentage of the short-circuit position
Step 4 Set the DC switch to OFF and check whether the connector or DC cable between
the possible faulty PV modules and the corresponding optimizers, or those
between the adjacent PV modules and the corresponding optimizers are damaged.
ɲ /©ăäȀàÝÃì¯ÉªÑÊÊìÑàÑàÃȀäìì¯äý²ì¯ìÑKEȀ
and view the alarm information.
If the Low Insulation Resistance alarm is not reported one minute after
the DC is supplied, the inspection on the PV string is complete. Choose
Device Commissioning > Maintenance > Inverter ON/OFF on the app
SUN2000-(2KTL-6KTL)-L1
User Manual E Locating Insulation Resistance Faults
Issue 03 (2020-09-15) Copyright © Huawei Technologies Co., Ltd. 110

Table of Contents

Other manuals for Huawei SUN2000-(2KTL-6KTL)-L1

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Huawei SUN2000-(2KTL-6KTL)-L1 and is the answer not in the manual?

Huawei SUN2000-(2KTL-6KTL)-L1 Specifications

General IconGeneral
BrandHuawei
ModelSUN2000-(2KTL-6KTL)-L1
CategoryInverter
LanguageEnglish

Related product manuals