5
No.
Description
Source
1
Recommended: a
single
-phase AC circuit
breaker
Rated voltage ≥ 250 V AC
Rated current:
16 A (SUN2000-2KTL-L1)
25 A (SUN2000-3KTL-L1 and SUN2000-
3.68KTL-L1)
32 A (SUN2000-4KTL-L1, SUN2000-
4.6KTL-L1, SUN2000-5KTL-L1, and
SUN2000-6KTL-L1)
Installing the PE Cable
3.2
Ground
point
Do not connect the neutral wire to the enclosure as a PE cable. Otherwise, electric shocks may
occur.
The PE point at the AC output port is used only as a PE equipotential point, and cannot
substitute for the PE point on the enclosure.
Silica gel or paint must be applied around the ground terminal after the PE cable is connected.
It is recommended that the right ground point be used for grounding. The other ground point
is reserved.
If FE communication is used, install a WLAN-FE Smart Dongle (SDongleA-05). You need to
purchase the WLAN-FE Smart Dongle by yourself.
If 4G communication is used, install a 4G Smart Dongle (SDongleA-03). You need to
purchase the 4G Smart Dongle by yourself.