What does 'Grid voltage imbalance' mean on my Huawei SUN2000-30KTL-M3 Inverter?
- DDebra FarmerSep 6, 2025
A 'Grid voltage imbalance' alarm on your Huawei Inverter signifies that the difference between power grid phase voltages exceeds the upper threshold. If this alarm occurs occasionally, it may indicate a temporary abnormality in the power grid, and the inverter should recover automatically once the grid returns to normal. However, if the alarm persists, you should first check whether the power grid voltage is within the acceptable range. If it's not, contact the local power operator for assistance. If the voltage is within the acceptable range but the alarm continues for an extended period, inspect the AC output power cable connection. If the cable is correctly connected, yet the alarm persists and impacts the energy yield of the PV plant, you should also contact the local power operator.