the maximum voltage over 10 min (59.S1), maximum overvoltage (59.S2),
minimum undervoltage (27.S1), minimum undervoltage (27.S2), maximum
overfrequency (81.S1), maximum overfrequency (81.S2), minimum
underfrequency (81.S), and minimum underfrequency (81.S2).
Procedure
Step 1 On the home screen, choose Maintenance > IPS test to access the IPS test screen.
Step 2 Tap Start to start an IPS test. The SUN2000 detects maximum voltage over 10 min
(59.S1), maximum overvoltage (59.S2), minimum undervoltage (27.S1), minimum
undervoltage (27.S2), maximum overfrequency (81.S1), maximum overfrequency
(81.S2), and minimum underfrequency (81.S1), and minimum underfrequency
(81.S2).
Figure 7-18 IPS test
Table 7-5 IPS test type
IPS Test Type
Description
Maximum voltage
over 10 min
(59.S1)
The default maximum voltage over 10 min protection
threshold is 253 V (1.10 Vn), and the default protection
time threshold is 3s.
Maximum
overvoltage
(59.S2)
The default overvoltage protection threshold is 264.5 V
(1.15 Vn), and the default protection time threshold is 0.2s.
SUN2000-(3KTL-10KTL)-M1 Series
User Manual 7 Man-Machine Interaction
Issue 17 (2024-01-12) Copyright © Huawei Technologies Co., Ltd. 100

Table of Contents

Other manuals for Huawei SUN2000-5KTL-M1

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Huawei SUN2000-5KTL-M1 and is the answer not in the manual?

Huawei SUN2000-5KTL-M1 Specifications

General IconGeneral
Max. Efficiency98.4%
Rated AC Output Power5000 W
Max. Apparent Power5500 VA
Max. DC Input Voltage1100 V
Number of MPPTs2
Operating Temperature Range-25°C to +60°C
Start Voltage200 V
European Efficiency97.8%
Protection DegreeIP65
Start-up Voltage200 V
Output Voltage Range180 V - 280 V
Frequency Range50 Hz / 60 Hz
Power Factor0.8 leading ... 0.8 lagging
THD<3%
Cooling MethodNatural Convection
Max. DC Power7500 W
Rated AC Voltage230 V