NO TICE
The solar inverter has an RCMU inside. Its external AC switch should be a three-
phase circuit breaker or other AC load circuit breakers to safely disconnect the
solar inverter from the power grid.
NO TE
The cable diameter must comply with local cable standards.
The factors that
aect cable selection include the rated current, cable type, routing
mode, ambient temperature, and maximum expected line loss.
Table 5-2 Cable description of a 3-pin model (S: cross-sectional area of the AC cable conductor; S
p
:
cross-sectional area of the protective earthing cable conductor)
No. Cable Category Conductor
Cross-Sectional
Area Range
Outer
Diameter
Source
1 DC input
power cable
PV cable that meets the
1100 V standard
4–6 mm
2
5.5–9 mm Prepared by
the
customer
2 RS485
communicatio
ns cable
Outdoor shielded twisted
pair that meets the local
standard
0.25–1 mm
2
One or
two
commu
nication
s cables:
4–11
mm
Three
commu
nication
s cables:
4–8 mm
Prepared by
the
customer
3 Protective
earthing (PE)
cable
[1]
Single-core outdoor
copper cable and M10
OT/DT terminals
S
p
≥ S/2 N/A Prepared by
the
customer
4 Tracking
system power
cable
Three-core outdoor
copper cable with dual-
layer protection
10 mm
2
15–18 mm Prepared by
the
customer
SUN2000-(75KTL, 100KTL, 110KTL, 125KTL) Series
User Manual 5 Electrical Connections
Issue 15 (2023-01-31) Copyright © Huawei Technologies Co., Ltd. 51

Table of Contents