5.6 Connecting an AC Output Power Cable
Prerequisites
To ensure that the inverter can be safely disconnected from the power grid
when an exception occurs, connect an AC switch to the AC side of the inverter.
Select an appropriate AC switch in accordance with local industry standards
and regulations.
Connect the AC output power cable according to the requirements
specied
by local power grid operators.
Connect the power cable of the tracking system before the AC output power
cable. Otherwise, reworking will be caused.
Figure 5-12 Cable connection sequence
(1) Power cable of the tracking system
(2) AC output power cable
WARNING
Do not connect loads between the inverter and the AC switch that directly
connects to the inverter. Otherwise, the switch may trip by mistake.
If an AC switch is used with specications beyond local standards, regulations,
or the Company's recommendations, the switch may fail to turn o in a timely
manner in case of exceptions, causing serious faults.
CA UTION
Each inverter must be equipped with an AC output switch. Multiple inverters
cannot connect to the same AC output switch.
SUN2000-(75KTL, 100KTL, 110KTL, 125KTL) Series
User Manual 5 Electrical Connections
Issue 15 (2023-01-31) Copyright © Huawei Technologies Co., Ltd. 60