NO TE
In the SmartLogger networking scenario, the Smart Dongle cannot be connected.
A maximum of 80 devices can connect to a single SmartLogger, such as inverters,
Smart Power sensor, and EMI. You are advised to connect fewer than 30 devices to
each RS485 route.
The Smart Power Sensor is necessary for export limitation. Select the Smart Power
Sensor according to the actual project.
To ensure the system response speed, you can connect the Smart Power Sensor to
a separate COM port.
5.7.1 Connecting the RS485 Communications Cable (Inverter
Cascading)
Procedure
Step 1 Connect the signal cable to the signal cable connector.
Figure 5-20 Installing the cable
Step 2 Connect the signal cable connector to the COM port.
SUN2000-(8KTL-20KTL)-M2
User Manual 5 Electrical Connections
Issue 11 (2023-02-07) Copyright © Huawei Technologies Co., Ltd. 56