(1) Shielding layer of the signal cable
NO TE
The DTSU666-HW and YDS60-80 power meters support a maximum current of 80 A.
SUN2000MA V100R001C00SPC146 and later versions can connect to YDS60-80 power
meters.
SUN2000MA V100R001C00SPC142 and later versions can connect to DTSU666-HW
power meters.
SUN2000MA V100R001C00SPC150 and later versions can connect to YDS60-C24 power
meters.
If the SUN2000-(2KTL-6KTL)-L1 are cascaded with three-phase inverters, they must be
connected to the grid in the same phase.
For a three-phase three-wire system, you need to set the cable connection mode.
Otherwise, the displayed voltage is incorrect.
Ensure that the baud rates of the DTSU666-H and YDS60-C24 meters are set to the
default values. If they are changed, meters may go
oine, generate alarms, or aect
the inverter output power.
Table 5-4 Select the cable connection mode
Paramet
er
Note
Select the cable connection mode:
0: n.34 indicates three-phase four-wire. 1: n.33 indicates three-phase
three-wire.
Procedure
Step 1 Connect the signal cable to the signal cable connector.
SUN2000-(8KTL-20KTL)-M2
User Manual 5 Electrical Connections
Issue 11 (2023-02-07) Copyright © Huawei Technologies Co., Ltd. 63