Description of Functions Available in the Installer Menu
Installer 1 [uC 0] Set UL Usage Class: This menu item is used to set the UL usage class, which
must be set by the installer before the operator will function. See page 17, step 2.
Installer 2 [Fd 0] Load Factory Defaults: This menu item is used to globally restore all menu
settings back to new machine status. To activate, change the setting 0 to 1 and push the Menu button.
The UL usage class and the hand configuration will need to be set again.
Installer 3 [dg 0] Set Solo, Master or Slave type: This menu item is used to configure an operator
as a Master or a Slave operator in Master/Slave paired gate installations.
Installer 4 [Ch 0] Set AC Charger or Solar: This menu item only appears on 24 VDC battery
machines only and is set to solar only when there is no AC battery charger.
Installer 5 [Fo 0] Enable Fire Dept. Open: This menu item is used to enable the Fire Dept. Open
input. When set to [Fo_1] this input will override vehicle detectors, photo eyes and gate edges to open a
gate. A reset input is required before the gate can be closed.
Installer 6 [oC 0] Enable Emergency Close: This menu item is used to enable the Emergency
Close input. When set to [oC_1] this input will, with a constant hold input, override vehicle detectors,
photo eyes and gate edges to close a gate. A reset input is required before the gate can be opened.
Installer 7 [SE 6] Inherent Sensor sensitivity:. This menu item is to adjust the sensitivity of the
internal inherent sensor. Available settings are 1-9, with 9 being the least sensitive.
Installer 8 [SS 0] Inherent Sensor function: This menu item is only available in UL class 4
operators and allows an option whereby the inherent sensor will only stop the gate.
Installer 9 [LC 0] Leaf delay Close: This menu item only appears if the operator is set up as a Master
or a Slave. Available settings are 1-7. Each increment adds ½ second, to a maximum of 3 ½ seconds
time delay, before the operator activates when commanded to close.
Installer 10 [Lo 0] Leaf delay Open: This menu item only appears if the operator is set up as a
Master or a Slave. Available settings are 1-7. Each increment adds ½ second, to a maximum of 3 ½
seconds time delay, before the operator activates when commanded to open.
Installer 11 [rt 0] Maximum run timer: The maximum run timer has a default setting of 60 seconds.
This menu item allows an optional setting of 300 seconds, if changed to [rt_1].
Installer 12 [EC 0] PEC (photo eye close) reverse to open: The default for this menu item is for
non-reversal if the close photo eye is triggered. The optional setting of [EC_1] will cause the gate to
reverse to open for two seconds if triggered while closing.
Installer 13 [PC 0] Set PEC – NO/NC: The default for this menu item is for photo eyes with Normally
Open outputs. The optional setting of [PC_1] will require a Normally Closed output. If set for N.C. the
connection is also supervised and any open or short circuit fault will generate a FAL2 alert, which
requires a Stop button reset to re-enable any function if triggered.
Installer 14 [gC 0] Set Edge input – NO/NC: The default for this menu item is for edge sensor with
Normally Open outputs. The optional setting of [gC_1] will require a N.C. output.