IBC Technologies Inc. 45 VFC 15-150 and VFC 45-225
4.3.3 Troubleshooting using the Control
Note: Never attempt to repair the control module. If the control module is
defective, replace it immediately.
Airflow Error
LCD Screen Message:
Error – Insufficient Air Flow -
Check Venting
Insufficient combustion airflow; soft error; will retry in
5 minutes
Check fan operation
Check lead is attached at fan
Cycle power off/on; listen for fan initialization. If
no action, focus your attention on the fan itself
Check for fouled reference
lines and air sensor
Check clear vinyl air reference lines below gas
valve for any sign of water. After disconnecting
from black sensor, blow clear. Check for exhaust
re-ingestion, or repeated power interruptions
Ensure condensate trap is not blocked
Go to Advanced Diagnostics and check differential
air pressure sensor (at rest and with fan on – see
Section 4.3.2.3)
Check achieved fan power
In Advanced Diagnostics, during Pre-purge, Fan
Pressure (FP) should move close to Required
Pressure (RP); if FP only 120-150 vs. RP of 250 or
300, then check for actual vent system blockage: (a)
disconnect intake within boiler case; (b) open
burner then fan/gas valve looking for debris
Water noise in vent.
Excess condensate in venting.
Check condensate trap for obstructions. Remove
obstructions and refill condensate trap with water.
Check vent length, size and configuration,
particularly re: horizontal 2” piping.
Waterflow Error
LCD Screen Message
Error - No Water Flow
Low water flow – soft error; will retry in 5 minutes
Check pressure sensors
Check wiring: water pressure sensors to controller.
Check pressure sensors - see Section 4.3.2.4
(2
nd
para)
Check for proper piping
Refer to Section 1.5 - Water Piping for
recommended piping installation.
Check primary pump
If there is a valve on the primary loop, close it and
listen for cavitation (evidence flow). If not, go to
Installer Setup; select pump purge “on” to run
pumps without a heat call - check for heat buildup
at pump body (indicates no flow).
Check for restriction in water
pipe.
Check temperature differential across heat
exchanger at low –medium firing rate if possible.
Examine air strainer components for scale