EasyManuals Logo

IBC SL 26-260 G3 Installation And Operating Instructions

IBC SL 26-260 G3
88 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #30 background imageLoading...
Page #30 background image
INSTALLATION AND OPERATION INSTRUCTIONS
1-22
SL 80-399 MODULATING GAS BOILER
SL 26-260 G3, SL 40-399 G3 MODULATING GAS BOILERS
Fluid ll is most often accomplished by using a boiler regulator & ll valve set at 12 psig
or more, with the appropriate backow prevention device as required by local code. This
is acceptable in areas where municipal water or well water has been treated and ltered
to remove excessive minerals and sediment, and water chemistry is known to be suitable
for closed loop hydronic systems. In areas where water quality is in question, or when
chemical treatment or glycol is required, other options should be considered. Follow the
applicable codes and good piping practice.
There are a number of boiler feed and pressurization devices on the market today that
may be a better choice than a raw water ll from the mains. When regular maintenance
requires relief valve blow-off, the discharge may be directed back into the pressurization
unit for recycling of boiler uid and chemicals back into the system. In buildings that may
be unoccupied for long periods of time, pressurization units are useful to prevent ood
damage should leakage occur from any component in the system. An additional benet is
that backow prevention devices are not required when using these devices.
Do not place any water connections above the boiler; leaks can damage the fan and
controls. If needed, create a shield over the top of the cover, but allow clearance for airow
and service access.
For best results, use a Primary/Secondary piping system, with a pumped boiler loop using
2" piping. Refer to Tables 5A and 5B for boiler head loss information.
For example, the minimum ow rate required through the heat exchanger is 20 gpm and
a maximum of 45 gpm is allowed. Primary/Secondary piping ensures adequate ow and
de-couples Δ°T issues (boiler vs. distribution). Aim for a 20° to 30° F Δ°T across the heat
exchanger at high re (there is a boiler protection throttle fence limiting the Δ°T to 40°F).
Figure 27: Primary/Secondary piping concept with hydraulic separator
The boilers can supply multiple heating loads with compatible supply temperature
requirements. Always ensure that loads sensitive to high temperatures are protected using
means such as mixing valves.
Supply stack upper tapping - 3/4”
FIP to accept relief valve and air
vent assembly
Relief valve and air vent assembly
(recommended conguration)
WARNING
Close ll valve after any addition
of water to the system, to reduce
risk of water escapement.
NOTE
Full sized application drawings
can be downloaded from our web
site.
www.ibcboiler.com

Table of Contents

Other manuals for IBC SL 26-260 G3

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the IBC SL 26-260 G3 and is the answer not in the manual?

IBC SL 26-260 G3 Specifications

General IconGeneral
BrandIBC
ModelSL 26-260 G3
CategoryBoiler
LanguageEnglish

Related product manuals