ERROR CODE
FULL indicator (yellow) flashing:
1. Water Supply Issue: High-level float detects water
10 minutes sooner than the low-level float.
Possible cause checklist
Check that the float(s) are properly installed.
Check that the float(s) are working properly.
Check all wire connections between the float(s)
and the control board (PCB).
ERROR CODE
ERROR indicator (red) flashing:
1. High Pressure Issue: High pressure switch open for
more than 10 seconds.
2. High Pressure Issue: High pressure switch open for
more than 10 seconds, 3 consecutive times.
Possible cause checklist
Check that the air filter or condenser is not dirty.
Check that the ambient air temp is below 100°F.
Check that there are no restrictions to air flow.
Check that discharge air is not being recirculated.
Check the refrigerant charge.
Check that the hot gas valve is working properly.
64