94
Suction Pressure High Checklist
Improper Installation
• Refer to “Installation/Visual Inspection Checklist” on
page 87.
Discharge Pressure
• Discharge pressure is too high, and is affecting suction
pressure, refer to “Discharge Pressure High Checklist”
on page 92.
Improper Refrigerant Charge
• Overcharged
• Wrong type of refrigerant
• Non-condensible in system
Other
• Non-Icetro components in system
• Hot Gas valve leaking
• TXV flooding (check bulb mounting)
• Defective compressor