20
FILTER
DIFF
ROOM
SET
REMOTE
4. Temperature Scale (F or C) – Choose Fahrenheit or Celsius.
Press the or button to select.
Press the
SW6
button to advance to the next screen.
FILTER
DIFF
ROOM
SET
REMOTE
5. 1
st
Stage Temperature Differential
(1°F to 3°F) (0.5°C to 1.5°C)
Set the number of degrees between your “setpoint”
temperature and your “turn on” temperature.
Press the or button to set differential value.
Press the
SW6
button to advance to the next screen.
FILTER
DIFF
ROOM
SET
REMOTE
FILTER
DIFF
ROOM
SET
REMOTE
3. Reversing Valve (O-Active or B-Active) – (Appears for
heat pump systems only)
Change between “o” (O-Active) and “b” (B-Active).
Press the or button to set reversing valve setting.
Press the
SW6
button to advance to the next screen.
FILTER
DIFF
ROOM
SET
REMOTE
6. 2
nd
Stage Temperature Differential
(1°F to 6°F) (0.5°C to 3.0°C)
Set the number of degrees between when stage 1 turns on
and when stage 2 turns on.
Press the or button to set differential value.
Press the
SW6
button to advance to the next screen.
FILTER
DIFF
ROOM
SET
REMOTE
FILTER
DIFF
ROOM
SET
REMOTE
FILTER
DIFF
ROOM
SET
REMOTE
7. Minimum Cool Setpoint
(45°F to 75°F) (7°C to 24.0°C)
Adjust to control the minimum Cool set temperature allowed.
Press the or button to select.
Press the
SW6 button
to advance to the next screen.