EasyManuals Logo

ICP A3 Series User Manual

ICP A3 Series
36 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #12 background imageLoading...
Page #12 background image
SERVICE AND TECHNICAL SUPPORT MANUAL Gas Furnace: (F/G)9MVE
Specifications subject to change without notice.
12 440 04 4801 03
1. Remove jumpers from R and W/W1.
2. Wait until the blower off delay is completed.
3. Turn 115 VAC power off.
4. Check the position of Set up switch SW1-3. When set to
ON, airflow is raised 18% for Low Heat. Factory default
position is OFF.
5. Turn 115 VAC power on.MN7A
6. Re--check Low Heat Temperature Rise
To lock the furnace in High Heat:
1. Connect a jumper across R and W/W1 and W2 at the
thermostat terminals at the furnace control.
2. Allow the burners to ignite and the blower to turn on.
3. Allow the supply temperature to stabilize and verify the
proper rise range.
If the temperature rise is too high or too low in High Heat:
1. Remove jumpers from R and W/W1 and W2.
2. Wait until the blower off delay is completed.
3. Turn 115 VAC power off.
4. Check the position of Set up switch SW1-4. When set to
OFF and SW1-3 is set to OFF, airflow is raised 7% for
Low Heat and 10% for High Heat. Factory default
position is ON. If SW1-3 is ON and SW1-4 is OFF, airflow
is raised 18% for Low Heat and 10% for High Heat
5. Turn 115 VAC power on.
6. Re-check High Heat Temperature Rise.
After the temperature rise has been verified:
1. Remove jumpers from thermostat terminals.
2. Allow the blower off delay to complete.
3. Turn Set up switches SW1-2 to the desired position.
4. Proceed to “Adjust Blower Off Delay” or install blower
door if complete
.
FIRE HAZARD
Failure to follow this warning could result in personal injury,
death, and/or property damage.
Reinstall manifold pressure tap plug in gas valve to
prevent gas leak.
!
WARNING
FURNACE OVERHEATING HAZARD
Failure to follow this caution may result in reduced furnace
life.
Recheck temperature rise. It must be within limits specified
on the rating plate. Recommended operation is at the
midpoint of rise range or slightly above.
CAUTION
!
Adjust Blower Off Delay (Heat Mode)
a. Remove blower door if installed.
b. Turn Dip switch SW17 or SW18 ON or OFF for
desired blower off delay. (See Table 4 and Figure 4,
Figure 5)
Table 4 Blower Speed Taps
DESIRED HEATING MODE
BLOWER OFF DELAY
(SEC.)
SETUP SWITCH (SW1-7 and -8)
POSITION
90 OFF OFF
120 ON OFF
150 OFF ON
180 ON ON
Adjust Cooling Airflow HighSpeed and
LowSpeed Cooling
The ECM blower can be adjusted for a range of airflows for
lowspeed or highspeed cooling. See Table 5Air Delivery
CFM (with Filter) and Figure 5. Furnace Setup Switches and
Descriptions. Depending on the model size, the cooling airflow
can be adjusted from 1.5 tons to 6 tons of nominal cooling
based on 350 CFM ton.
NOTE: 6 ton airflow will truncate at 2200 CFM on applicable
models.
The highspeed or singlespeed cooling airflow is adjusted by
turning setup switches SW26, SW27 and SW28 either ON
or OFF. Select the required airflow from Table 5. Table 5 is
based on 350 CFM per ton. For other CFM per ton setup switch
selections, see Figure 4, Figure 5 and Figure 16.
The Continuous Fan airflow selection via setup switches
SW23, SW24 and SW25 is also the airflow for lowspeed
cooling when the furnace is used with a twospeed cooling or
heat pump unit. Adjust the Continuous Fan CFM setup
switches SW23, SW24 and SW25 to match the airflow
required for lowspeed cooling. Select the required airflow from
Table 5 and Figure 5.
NOTE: The airflow selected via SW23, SW24 and SW25
(lowspeed cooling airflow) cannot exceed the airflow selected
via SW26, SW27 and SW28 (highspeed cooling airflow).
For other CFM per ton setup switch selections, see Figure 4
and Figure 5.
For a complete explanation of cooling airflow, refer to the
section titled “Sequence of Operation.”
Adjust Continuous Fan Airflow/Low Speed
Cooling Airflow
NOTE: When the furnace is used with a twospeed cooling or
heat pump unit, the airflow selected for Continuous Fan via
setup switch SW23, SW24 and SW25 will also be the
airflow used for lowspeed cooling, and vice versa.
NOTE: When the furnace is used with a twospeed cooling or
heat pump unit, adjust the Continuous Fan CFM setup
switches SW23, SW24 and SW25 to match the airflow
required for lowspeed cooling.
Select the required Continuous Fan airflow using setup
switches SW23, SW24 and SW25 as shown in Figure 5
and Table 5.

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the ICP A3 Series and is the answer not in the manual?

ICP A3 Series Specifications

General IconGeneral
BrandICP
ModelA3 Series
CategoryFurnace
LanguageEnglish

Related product manuals