101
CHAPTER 19
CHAPTER 19 - PRODUCT SPECIFICATIONS
Boiler Model Fuel Input (Btu/h)
DOE Heating
Capacity (Btu/h)
Net AHRI Rat-
ing (Btu/h)
AFUE
Unpackaged
Weight Lbs (Kg)
Shipping
Weight Lbs
(Kg)
EXALT 110 Solo
Natural
Propane
13,750 –
110,000
102,000 89,000 95% 85 (38.5) 102 (46)
EXALT 155 Solo
Natural
Propane
19,375 –
155,000
143,000 124,000 95% 98 (44.5) 116 (52)
EXALT 199 Solo
Natural
Propane
24,875 –
199,000
185,000 161,000 95% 108 (49) 126 (56.5)
EXALT 155 combi
Natural
Propane
19,375 –
155,000
143,000 124,000 95% 121 (55) 134 (63)
EXALT 199 combi
Natural
Propane
24,875 –
199,000
185,000 161,000 95% 132 (60) 150 (68)
• The heating capacity of the EXALT Solo 110/155/199 and EXALT Combi
155/199 is based on the test requirements of the U.S. Department of Energy.
• The AHRI rating is based on a piping and pick up allowance of 1.15.
This allowance should be sufficient for standard radiation requirements.
• Based on the given AFUE the EXALT Solo 110/155/199 and EXALT Combi
155/199 meet the energy efficiency guidelines established by Energy Star.
• Input and output ratings are shown for sea level applications. The EXALT
features altitude compensation, altitude of the boiler installation must be
inputted via the EXALT menu. Failure in selecting the correct altitude may
compromise boiler ignition performance and will derate the boiler by 1.7%
per 1000ft above sea level.
NOTICE
Combi Water Heater Performance
155 Combi 199 Combi
DHW Output GPM (70°F Rise) 4.0 5.3
DHW Output GPM (75°F Rise) 3.7 4.9
DHW Output GPM (80°F Rise) 3.5 4.6
DHW Minimum Flow Rate (GPM) 0.5 0.5