14
6 Electrical connection
The unit must be connected by a qualified electrician�
The national and international regulations for the installation of electrical
equipment must be adhered to�
Voltage supply according to EN 50178, SELV, PELV�
The unit is supplied with 24 V DC (18���32 V DC) low voltage�
The voltage supply must comply with the provisions of protective low
voltage EN 50178, SELV, PELV�
► Disconnect power�
► Connect the unit as follows:
4
2 1
3
5
BK: black
BN: brown
BU: blue
GY: grey
WH: white
Colours to DIN EN 60947-5-2
Pin 1 L+
Pin 2 (OUT2) analogue output
Pin 3 L-
Pin 4 (OUT1)
switching output
IO-Link
Pin 5 test input
► Use a screened cable� The screen of the cable must be connected to
the sensor housing�
When inductive loads are switched:
► Use a free wheel diode�