EasyManua.ls Logo

IFM CompactModule CR2032 - Fault Correction and Diagnostics; EMCY Object Error Codes

IFM CompactModule CR2032
29 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
UK
CompactModul Metall CR2032
17
Steuerungssysteme
ifm electronic gmbh • Friedrichstraße 1 • 45128 Essen
14.08.2014We reserve the right to make technical alterations without prior notice. CR2032 / page 5
Input Output
CODESYS 2.3
PLC Configuration
CODESYS 2.3
PLC Configuration
binary inputs Channel #
LED
Pin Pin Channel #
LED
binary
outputs
analogue
outputs
7 8
chan 4
o
24
o
Bit 3 chan 4
chan 4
o
42
o
Bit 7
5 6
chan 3
o
24
o
Bit 2
chan 3
chan 3
o
42
o
Bit 6
3 4
chan 2
o
24
o
Bit 1
chan 2
chan 2
o
42
o
Bit 5
1 2
chan 1
o
24
o
Bit 0
chan 1
chan 1
o
42
o
Bit 4
CR2032 Assignment of the LEDs to the connections
10 Fault correction
10.1 EMCY Object
The following error codes to DSP-401 and DSP-301 are supported:
EMCY Code Error Reg Additional
Code
Description
0x3300 0x05 0x00 "Output Voltage"
Supply voltage V
BBO
of the outputs is missing
0x6100 0x11 0x00 "Internal Software“ Overflow of a Tx queue,
e�g� frequency of the RxPDOs is too high�
Only external reset via an entry in 1003 00
0x6101 0x11 0x00 "Internal Software"
Overflow of a Tx queue
e�g� device does not communicate with the bus�
Only external reset via an entry in 1003 00
0x8000 0x11 0x00 "Monitoring" (Synch Error)
For "communication cycle" no synch object is re-
ceived (only in OPERATIONAL)�
Reset with the next synch OBJ or PREOP