1.16 INSTALLATION OF VERTICAL
TERMINALS 80 Ø.
Configuration type B, open chamber and
forced draught.
80 Ø Vertical kit (plastic for indoor applica-
tions).
Kit assembly (Fig. 1-14): install the 80 Ø terminal
(2) on the central hole on the boiler up to stop,
making sure that the wall sealing plates (1) have
been tted. is will ensure the sealing eciency
of the kit components.
Maximum length (MAX L) (Fig. 1-15). e kit
with this conguration can be extended up to
a max. measurement of 24.0 m with Victrix Pro
35 2ErP and 30.0 m with Victrix Pro 55 2ErP,
including the terminal.
Using the Ø 80 vertical terminal for direct dis-
charge of the combustion products, the terminal
must be shortened (see quotas g. 1-16). e wall
sealing plate (1) must also be inserted in this case
going up to stop on the boiler cover.
80 Ø Vertical kit (steel for outdoor applica-
tions).
Kit assembly (Fig. 1-17): install the 80 Ø terminal
(1) on the central hole on the boiler up to the
stop, ensuring the sealing eciency of the kit
components.
e 80 Ø steel terminal is used to install the boiler
outdoors with a direct exhaust. e terminal
cannot be shortened and once it is installed it
will extend out by 630 mm (Fig. 1-18).