BOILER COMMISSIONING
INITIAL CHECK
To commission the boiler:
- make sure that the declaration of conformity
for installation is supplied with the appliance;
- make sure that the type of gas used corresponds
to boiler settings;
- check connection to a 230V-50Hz power
mains, correct L-N polarity and the earthing
connection;
- switch the boiler on and check correct ignition;
- check the CO
2
in the fumes at maximum and
minimum ow rate;
- make sure the fan rpm matches the value pro-
vided in the book (Par. 3.23);
- check activation of the safety device in the event
of no gas, as well as the relative activation time;
- check the intervention of the main switch
located upstream of the boiler and in the boiler;
- check the existing draught during normal
functioning of the appliance, e.g. a draught
gauge positioned at the exit of the appliance
combustion products;
- check that there is no backow of combustion
products into the room, even during function-
ing of fans;
- check that the intake and/or exhaust terminals
are not blocked;
- ensure activation of all adjustment devices;
- seal the gas ow rate regulation devices (if
settings are modied);
- check sealing eciency of water circuits;
- check ventilation and/or aeration of the instal-
lation room where provided.
If even only a single safety check oers a negative
result, do not commission the system.
3.1 HYDRAULIC DIAGRAM.
Key:
1 - Draining funnel on view
2 - Boiler draining valve
3 - 4 bar safety valve
4 - Flow manifold
5 - Condensate trap siphon
6 - Gas valve
7 - Gas nozzle
8 - Air fan
9 - Manifold cover
10 - Ignition electrode
11 - Condensation module cover
12 - Condensation module
13 - Flue probe
14 - Condensing module air vent valve
15 - ermofuse
16 - Air sample point
17 - Flue sample point
18 - Venturi positive sign (P2)
19 - Fumes hood
20 - Heat-exchanger safety thermostat
(manual reset)
21 - Over temperature safety thermostat
22 - System return regulation probe
23 - System ow regulation probe
24 - Detection electrode
25 - System ow meter
26 - Burner
27 - Air intake pipe
28 - Sleeve with seats for Venturi
29 - Automatic vent valve
30 - Boiler circulator pump
M - System ow
SC - Condensate drain
G - Gas supply
R - System return