31
INSTALLERUSER
MAINTENANCE TECHNICIAN
Programming menu
Menu item Description Adjustment range Default value
Customised
Value
P01
Set Risc (CH Set) is denes the boiler's ow temperature during heating 20 ÷ P02 °C 85
P02
Set risc Max (Max
CH Set)
is denes the maximum settable ow temperature during heating 20 ÷ 95 °C 85
P03
Isteresi
riscaldamento
(Heating Hysteresis)
is denes the power-o hysteresis during the heating phase 2 ÷ 10 °C 5
P04
Anti cicli
riscaldamento (Anti-
cycle CH)
is is used to set a waiting time to avoid the boiler from switching on
multiple times and frequently during CH mode
0 ÷ 15 minutes 3 minutes
P05
Tempo min risc (CH
min time)
is is the amount of time that the boiler needs to stabilise, when the burner
runs at minimum power for the set amount of time
3 ÷ 10 minutes 3 minutes
P06
Rampa
riscaldamento (CH
ramp)
e amount of time that the boiler takes to reach the required temperature,
number of degrees per minute (0 means no ramp)
0 ÷ 60 °C/minute 4 °C/minute
P07
Post circolazione
riscaldamento (CH
post-circulation)
e amount of CH post circulation once the CH phase is fnished 1 ÷ 30 minutes 3 minutes
P08
Pot risc max
disponibile (Available
max heat out)
is denes the maximum power percentage to be used during the set CH
phase
P09 ÷ 100% 100%
P09
Pot risc min
disponibile (Available
max heat out)
is denes the minimum power percentage to be used during the set CH
phase
0 ÷ P08% 0%
P10
Minimum system
ow rate
is denes the minimum system ow rate required to power-on the boiler
Attention: do not change this parameter
5 ÷ 47 l/minutes 14 l/minutes
P11
Anti umidità elettrodi
(Electrodes anti-
humidity)
is denes fan speed and operating mode, to avoid humidity inside
the condensing module, which could otherwise cause the electrodes to
malfunction (0 = disabled function, recommended value = 40) (RPM speed is
calculated by multiplying the value displayed by 50)
P26 ÷120 0
P12
Boiler’s modulation
ratio
It denes the boiler’s modulation ratio
(Do not modify)
0 ÷ 100% 10%
P13
Boiler power Used to calculate the boiler power in the event of simple cascade. 0 ÷ 255 kW
35 kW = 35
55 kW = 50
P14
External probe curve
is is used to select the external probe operating curve (optional) (0 =
disabled probe)
0 ÷ 10 0
P15
External probe oset is denes the CH oset in relation to the selected external probe curve 20 ÷ 70 °C 30 °C
P16
Set San (DHW set) is denes the DHW temperature 20 ÷ 65 °C 65 °C
P17
P17 External D.H.W /
3-waypump
- With single boiler and common ow probe, it lets you choose between an
external D.H.W pump and a 3-way one.
- With a simple cascade, it manages a D.H.W. pump (downstream an
hydraulic separator).
0 = 3 Ways
1 = D.H.W. pump
P18
Isteresi sanitario
(DHW hysteresis)
is denes the DHW power-on hysteresis during CH 2 ÷ 10 °C 5 °C
P19
Post circolazione
sanitario (DHW post-
circulation)
is is the post circulation time during DHW once DHW production is
nished
0 ÷ 180 seconds 60 seconds
P20
Pot san max
disponibile (Available
max DHW pow)
is denes the maximum power percentage to be used during the set DHW
phase
P21 ÷ 100 % 50 %
P21
Pot san min
disponibile (Available
max DHW pow)
is denes the minimum power percentage to be used during the set DHW
phase
0 ÷ P20 % 0 %
P22
DHW ow
temperature with
thermostat
In combination with a storage tank and a separate thermostat, this denes the
ow temperature during DHW operation
35 ÷ 90 °C 80 °C
P23
Modulazione sanitario
(DHW modulation)
Summed with the “Set San” (P16) parameter, this denes the ow
temperature set that the boiler has to modulate the power on during DHW
5 ÷ 30 °C 15 °C
P24
Incremento o
sanitario (DHW o
increment)
is denes the time that the boiler allows the burner to switch o during
DHW, by an increment of 5 °C on top of the ow temperature
0 ÷ 255 seconds 60 seconds
P25
Velocità Max
ventilatore (Min fan
Speed)
is denes the max fan speed and therefore the maximum relative boiler
operating power (RPM speed is calculated by multiplying the value displayed
by 50)
P26 ÷ 255 RPM x 50
35 kW Met. 101
35 kW LPG 98
55 kW Met. 131
55 kW LPG 129