64
INSTALLER
USERMAINTENANCE TECHNICIAN
TECHNICAL DATA
Victrix Tera V2 28 EU
Gas type CO
2
to nominal Q. CO
2
to ignition Q. CO
2
to minimum Q.
G20 9,2 (9,1 ÷ 9,5) 9,1 (9,0 ÷ 9,4) 8,5 (8,3 ÷ 8,7)
G31 10,2 (10,0 ÷ 10,4) 10,2 (10,0 ÷ 10,4) 9,7 (9,5 ÷ 9,9)
Gas type O
2
at Nominal Q. O
2
at Ignition Q. O
2
at Minimum Q.
G20 4,4 (4,6 ÷ 3,9) 4,6 (4,8 ÷ 4,1) 5,7 (6,0 ÷ 5,3)
Victrix Tera V2 32 EU
Gas type CO
2
to nominal Q. CO
2
to ignition Q. CO
2
to minimum Q.
G20 9,2 (9,1 ÷ 9,5) 9,2 (9,1 ÷ 9,5) 8,6 (8,3 ÷ 8,7)
G31 10,3 (10,1 ÷ 10,5) 10,2 (10,1 ÷ 10,5) 9,6 (9,4 ÷ 9,8)
Gas type O
2
at Nominal Q. O
2
at Ignition Q. O
2
at Minimum Q.
G20 4,4 (4,6 ÷ 3,9) 4,5 (4,6 ÷ 3,9) 5,5 (6,0 ÷ 5,3)
Victrix Tera V2 38 EU
Gas type CO
2
to nominal Q. CO
2
to ignition Q. CO
2
to minimum Q.
G20 9,0 (8,9 ÷ 9,3) 9,0 (8,9 ÷ 9,3) 8,5 (8,2 ÷ 8,6)
G31 10,2 (10,1 ÷ 10,4) 10,2 (10,0 ÷ 10,4) 9,6 (9,4 ÷ 9,8)
Gas type O
2
at Nominal Q. O
2
at Ignition Q. O
2
at Minimum Q.
G20 4,8 (5,0 ÷ 4,2) 4,8 (5,0 ÷ 4,2) 5,7 (6,2 ÷ 5,5)
If a Hydrogen ready installation is planned for H
2
percentages up to 20%, (referring to the gas distributed in the network) all
calibration of the gas valve must refer to the O
2
values in the table above.
In addition to yearly maintenance, one must also check the energy eciency of the thermal system, with frequency and proce-
dures that comply with the indications of the technical regulations in force.
When adjusting Nominal Q., if the O
2
values are not reached with the gas ow regulator completely open, no further adjust-
ments are required.