AM340 - Visual inspection of the fire extinguishing system
Orientation
The fire extinguishing system must only be inspected directly by the manufacturer of
the extinguishing system or by a person authorized by the manufacturer.
The fire extinguishing system is still active even when the
machine is switched off!
Flash photography in the immediate vicinity of the sensors may
trigger the fire extinguishing system.
Procedure
1. Be sure to follow the manufacturer's documentation.
2.
Example: Inspection stickers Kraft & Bauer
Check sticker for manufacturing date.
3. Check sticker for inspection date.
4. Check sticker for battery replacement.
5. Log all work carried out in the service, inspection and maintenance schedules/
logs of the customer and the manufacturer.
Maintenance Summary - Care activities
46
Maintenance Instructions
MS40-8
DIM078EN - 02.06.2020