2-4. UPS Installation for a Parallel System
If the UPS is only available for single operation, you may skip this section to the next.
1) Install and wires the UPSs according to the section 2-3.
2) Connect the output wires of each UPS to an output breaker.
3) Connect all output breakers to a major output breaker. Then this major output breaker will directly connect to the
loads.
4) Each UPS is connected to an independent battery pack.
NOTE: The parallel system cannot use one battery pack. Otherwise, it will cause system permanent failure.
5) Refer to the following wiring diagram:
L1 L2
L
3
N
L
1
L
2
L
3
N
L
1
L2
L
3
N
L1 L2
L
3
N
L
1
L
2
L
3
N
L
1
L2
L
3
N
Wiring diagram of parallel system for 10K(S)/15K(S)/20K(S)

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the INFOSEC UPS SYSTEM E4 LCD 10K TT and is the answer not in the manual?

INFOSEC UPS SYSTEM E4 LCD 10K TT Specifications

General IconGeneral
BrandINFOSEC UPS SYSTEM
ModelE4 LCD 10K TT
CategoryUPS
LanguageEnglish

Related product manuals