3-10. Warning Indicator
Warning Icon (flashing) Alarm
Battery low
Beeping every second
Overload
Beeping twice every second
Battery unconnected
Beeping every second
Over charge
Beeping every second
EPO enable
Beeping every second
Fan failure/Over temperature
Beeping every second
Charger failure
Beeping every second
I/P fuse broken
Beeping every second
Overload 3 times in 30min
Beeping every second
3-11. Warning Codes
Warning code Warning event Warning code Warning event
01 Battery unconnected 10 L1 IP fuse broken*
02 IP Neutral loss 11 L2 IP fuse broken*
04 IP phase abnormal 12 L3 IP fuse broken*
05 Bypass phase abnormal 21
Line situations are different in parallel
system
07 Over charge 22
Bypass situations are different in parallel
system
08 Low battery 33
Locked in bypass after overload 3 times
in 30 minutes
09 Overload 34 Converter current unbalance
0A Fan failure 35 Battery fuse broken
0B EPO enable 3A Cover of maintain switch is open
0D Over temperature 3C Utility extremely unbalanced
0E Charger failure
3D Bypass unstable
* These alarms are only for the single input unit.