EasyManua.ls Logo

INFOSEC E4 Value Series - Technical Specifications

INFOSEC E4 Value Series
Print Icon
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
57
INFOSEC UPS SYSTEM 4 rue de la Rigotière 44700 Orvault France www.infosec-ups.com
Hot Line Tel : +33 (0)2 40 76 15 82 fax : +33(0)2 40 94 29 51 hotline@infosec.fr 03 16 AA 59 203 26
MODEL
E4 VALUE 4000
E4 VALUE 5000
E4 VALUE 5000 B+
E4 VALUE 6000
E4 VALUE 10k
CAPACITY*
4000 VA / 3200 W
5000 VA / 4000 W
5000 VA / 4000 W
6000 VA / 4800 W
10 kVA / 8000 W
INPUT
Input voltage
200/208/220/230/240VAC
Frequency range
46 Hz ~ 54 Hz ou 56 Hz ~ 64 Hz
Power factor
0.99 @ 100% load
OUTPUT
Output voltage
200/208/220/230/240VAC
Voltage Regulation
±1% (Batt. Mode)
Frequency range
46 Hz ~ 54 Hz ou 56 Hz ~ 64 Hz
Frequency range (batt
mode)
50 Hz ou 60 Hz +/- 0.1Hz
Current Crest Ratio
3:1
Harmonic Distortion
<= 3% THD (linear load); <= 5% THD (non-linear load)
Transfer
Time
AC Mode to
Batt. Mode
Zero
Inverter to
Bypass
4 ms (Typical)
Waveform
pure sinusoïdale
EFFICIENCY
AC Mode
92%
92%
93%
Battery Mode
89%
90%
91%
BATTERY
Battery type
12 V / 9 AH
Number
12
16
Recharge Time
9 hours recover to 90% capacity (Typical)
Charging Current
1.0 A / 2.0 A
Charging voltage
163.8 VDC ±1%
218.4 VDC ±1%
Backup time
From 5 to 30 min. depending on the connected load
PHYSICAL CHARACTERISTICS
Dimension, LxlxH (mm)
Net weight (kgs)
369 x 190 X 573
369 x 190 x 688
442 x 190 x 688
46
61
66
INDICATORS
LED
Load level, Battery level, AC mode, Battery mode, Bypass mode, and Fault indicator.
Alarms
Battery mode, Low battery, Overload, Fault
BYPASS
Bypass static
Yes
Bypass manual
Optional
ENVIRONMENT
Humidity
20-90 % RH @ 0- 40°C (non-condensing)
Noise level
Less than 50dBA @ 1 Meter
MANAGEMENT & COMMUNICATION
Communication port
USB / RS232
Software
Infopower included software (Supports Windows® 98/2000/2003/XP/Vista/2008,
Windows© 7,8, 10, Linux, and MAC)
SNMP (optional)
Optional SNMP I : power management from SNMP manager (VMware© compatible) and web browser
NORMS
Standard
CE RoHS
EMC
EN 62040-2 : 2006; EN 61000-4-2:2009; EN 61000-4-3:2006+A1:2008+A2:2010;
EN 61000-4-4:2004+A1:2010; EN 61000-4-5:2006; EN 61000-4-6:2009; EN
61000-4-8:2010; EN 61000-2-2:2002
LVD
EN 62040-1:2008+A1:2013
SALES INFORMATIONS
Warranty
2 years
Gencods
3700085 67426 0
3700085 67420 8
3700085 67423 9
3700085 67421 5
3700085 67422 2
* Derate capacity to 60% of capacity in CVCF mode and to 90% when the output voltage is adjusted to 208VAC.
Product specifications are subject to change without further notice.